Pressure Relief Valve deflagration- and endurance burning-proof

Function and Description

csm_fc92a9a3ad92c1daffd4bf7f5a5f169fdc8ec691_e0c965ba88 The deflagration-proof and endurance burning-proof BE/HR-D type PROTEGO® valve is a highly developed pressure relief valve with an integrated flame arrester unit. It is primarily used as a safety device for flame transmission proof outbreathing on tanks, containers and process engineering apparatus. The valve offers reliable protection against excess pressure and prevents product losses almost up to the set pressure; it also protects against atmospheric deflagration as well as endurance burning if stabilized burning occurs. The PROTEGO® flame arrester unit is designed to achieve minimum pressure drop with maximum safety. The BE/HR-D valve is available for substances of explosion group IIA (NEC group D MESG > 0.9 mm).

When the set pressure is reached, the valve starts to open and reaches full lift within 40% overpressure. The tank pressure is maintained up to the set pressure with a tightness that is far superior to the conventional standard due to our state of the art manufacturing technology. This feature is ensured by the valve seats made of high quality stainless steel and with individually lapped valve pallets (1) or with an air cushion seal (2) in conjunction with high quality FEP diaphragm. After the excess pressure is discharged, the valve reseats and provides a tight seal. If the set pressure is exceeded, explosive gas/product-vapour air mixtures are released to the atmosphere. If this mixture ignites, the integrated PROTEGO® flame arrester unit (3) prevents flame transmission into the tank. If additional mixture continues to flow and stabilized burning occurs, the integrated flame arrester unit prevents flashback as a result from endurance burning. The valve is protected and also fulfils its function under this severe service conditions. The spring loaded weather hood opens as soon as the fusible element (4) melts.

The valve can be used up to an operating temperature of +60°C / 140°F and meets the requirements of European tank design standard EN 14015 – Appendix L and ISO 28300 (API 2000).

Type-approved in accordance with the current ATEX Directive and EN ISO 16852 as well as other international standards.

Features and Advantages

  • requires only 40% overpressure to full lift
  • through 40% technology higher set pressures can be used which results in product loss reduction compared to conventional 100% overpressure technology vents (compare API 2000)
  • more design flexibility through higher reseating pressures; vents reseat when conventional vent is still discharging costly product or nitrogen
  • high performance seal reducing product loss below EPA’s 500ppm rule preventing environmental pollution
  • the valve disc is guided within the housing to protect against harsh weather conditions
  • can be used as protective system according to ATEX in areas subject to explosion hazards
  • high flow capacity through large FLAMEFILTER® crosssection, results in low pressure drop
  • FLAMEFILTER® provides protection against atmospheric deflagration and endurance burning
  • FLAMEFILTER® integrated into the valve saves space, weight and reduces cost
  • FLAMEFILTER® protected from clogging through product vapours
  • flame-transmission-proof condensate drain
  • maintenance-friendly design

Download

  • Dimensions

    To select the nominal size (DN), please use the flow capacity chart on the following page

    DN 150 / 6" 200 / 8"  
    NG 400 / 16" 400 / 16"  
    a 600 / 23.62 600 / 23.62  
    b 545 / 21.46 545 / 21.46  
    c 485 / 19.09 485 / 19.09 NG = Nominal size

    Dimensions in mm / inches

    csm_635de02c07bd7a3f50cd8ce9571177d1547883d8_131b072146

    csm_33d566b8591b7cf1b806b155a53fa32c82197652_8287b4a04e

    Detail X

    csm_617a2d97aac892825944001eee6024f36b85496b_2e12a3b258

    Detail X

  • Material selection for housing

    Design A B
    Housing Steel Stainless Steel
    Valve seat Stainless Steel Stainless Steel
    Weather Hood Steel Stainless Steel
    Flame arrester unit A B

    Special materials upon request

    Material combinations of flame arrester unit

    Design  A B
    FLAMEFILTER® cage Steel Stainless Steel
    FLAMEFILTER® Stainless Steel Stainless Steel

    Special materials upon request

    Material selection for valve pallet

    Design A B C
    Pressure range [mbar]
    [inch W.C.]
    +2.0 up to +3.5
    +0.8 up to +1.4
    >+3.5 up to +14
    >+1.4 up to +5.6
    >+14 up to +35
    >+5.6 up to +14
    Valve pallet Aluminium Stainless Steel Stainless Steel
    Sealing FEP FEP Metal to Metal

    Special materials and higher pressure settings upon request

    csm_635de02c07bd7a3f50cd8ce9571177d1547883d8_131b072146

    csm_33d566b8591b7cf1b806b155a53fa32c82197652_8287b4a04e

    Detail X

    csm_617a2d97aac892825944001eee6024f36b85496b_2e12a3b258

    Detail X

  • Selection of explosion group

    MESG Expl. Gr. (IEC / CEN) Gas Group (NEC)
    > 0,90 mm IIA D

    Special approvals upon request

    Flange connection type

    EN 1092-1; Form B1
    ASME B16.5; 150 lbs RFSF

    other types upon request

    Design Types and Specifications

    The valve disc is weight-loaded.

    Pressure relief valve, basic design

    BE/HR-D-400/...

    Additional special devices available upon request

    Settings

    Pressure:

    +2.0 mbar +35 mbar  
      +0.8 inch W.C. +14 inch W.C.  

    Higher pressure settings upon request.

    csm_635de02c07bd7a3f50cd8ce9571177d1547883d8_131b072146

    csm_33d566b8591b7cf1b806b155a53fa32c82197652_8287b4a04e

    Detail X

    csm_617a2d97aac892825944001eee6024f36b85496b_2e12a3b258

    Detail X

  • Flow Capacity Chart

    8d15f0be0c07d805251dfb8066daa04cc8e1e461

    c0fe4fb81c422b376b27b832accf100fd77f3fcf

    The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig. Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar). Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.

    csm_635de02c07bd7a3f50cd8ce9571177d1547883d8_131b072146

    csm_33d566b8591b7cf1b806b155a53fa32c82197652_8287b4a04e

    Detail X

    csm_617a2d97aac892825944001eee6024f36b85496b_2e12a3b258

    Detail X

Download
Телефон:
Feedback

Leave a request and we will contact you as soon as possible